TWR Products

DMCIP


Categories: Monitoring Products

  • Description

    The DMCIP Alarm Monitor is a highly sophisticated stand alone product that delivers quality monitoring at a reasonable price. Using TCP/IP, Verizon Wireless or AT&T Wireless modem to deliver alarms using Simple Network Management Protocol (SNMP), the Internet-standard protocol for managing devices on IP networks. The DMCIP has ten inputs that can be configured as: Alarm, Event or Normal for both the Normally Closed and Normally Opened conditions.

    The DMCIP has a built in photocell monitor that works with 120/240VAC or 5-24VDC photocells and has selectable day / night alarm timers and logs when the photocell changes from day to night and back to day. The cabinet door is monitored and can be used to generate an alarm for quarterly test or for tamper detection. When there is a power loss an on board circuit monitors the battery voltage disconnecting it before the voltage drops to low and causes damage to the backup battery.

    The DMCIP is designed to send SNMP Traps to an existing NMS management system or can be monitored by TWR. A DMCIP SNMP Configuration Utility is supplied to allow easy configuration and interrogated through the on-board Ethernet or modem wireless interface. With this interface the alarm conditions you set can be viewed at any time.
  • Key Features

    • 10 Standard alarm inputs - expandable
    • Photocell monitoring
    • AC Power monitoring
    • Cabinet temperature
    • Backup battery discharge protection
  • Specs

    • Dimensions (LxWxH): 12" x 10" x 6" (30 x 25.4 x 15.24 cm)
    • Weight: 10.3 lbs (4.67 kg)
    • NEMA 4 Enclosure
    • Input Voltage: 120V - 240V AC, 24V DC
    • Operating temperature range: -40°C to +70°C
    • Humidity: 5 - 95% Non-condensing
  • Options

    DMCIP/Monitoring Options

    • CDMA Wireless Modem
    • GPRS Wireless Modem
    • Ethernet TCP/IP Modem
    • NOC Software
    • Analog Inputs
    • SNMP